Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM05293
Parcel: 110113620

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM05293
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation for the restroom exhaust fans, EF-1,& EF-2, so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
07/25/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
Also provide a written response.
#1. There are issues with the restroom exhaust fans per the mechanical plan reviewer comments that may effect the electrical design..Or require a change in operation.
Ref: 2012 IBC sec 107.2.1, 2011 NEC