Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM05293
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05293
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2017 ANDREW CONNOR ZONING REVIEW Approved
07/11/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation for the restroom exhaust fans, EF-1,& EF-2, so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
07/11/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/11/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/11/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/11/2017 ROBERT SHERRY WATER REVIEW Completed
07/11/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/12/2017 MARTIN BROWN FIRE REVIEW Approved
07/12/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Completed
07/14/2017 GERRY KOZIOL WWM REVIEW Completed P17WX01705