Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05293
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/11/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
07/11/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the sequence of operation for the restroom exhaust fans, EF-1,& EF-2, so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012. |
07/11/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
07/11/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
07/11/2017 | TPROBAS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/11/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/11/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
07/12/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/12/2017 | TPROBAS1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
07/14/2017 | GERRY KOZIOL | WWM | REVIEW | Completed | P17WX01705 |