Permit Number: T17CM05289
Parcel: 13327001D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM05289
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A501; original Comment 6: Sheet A501 in Wall Section 1, references are made to Wall Section 3/A501 in 2 separate locations. Should this reference Details on Sheet A502 instead? Verify and revise as necessary.
2. Sheet A502; original Comment 7(partial): Sheet A502 Wall Sections 14 & 16, indicate the type, size and number of fasteners to be used for the bracing.
08/31/2017 STEVE SHIELDS ZONING REVIEW Approved
09/19/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
As per the last electrical plan review comment, it was requested that the plans provided evidence that the exterior lighting will meet the requirements of the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE.
Deficiencies were found in the lumen calculations as follows, Ref; plan sheet E400;
(a) The note * , in reference to the 'A' luminaire is incorrect. This note requires 100% of luminaire output to be counted.
(b) The note ** calc, 175,000 is incorrect, should be 250,000 per option 2.
(c) The existing parking lot lighting ( EX ) must be included in the lumen calcs if they are within this parcel. 104.2, 104.2.1.
(d) The color temperature of the exterior light sources cannot exceed 3500 Kelvin. 402.1.
(e) Provide shielding information in the luminaire schedule or lumen cals. ( Full Cut Off, Unshielded, Other ). 104.2.1.
(f) Specify whether a special inspection is required. 106.2.1.