Permit Number: T17CM05289
Parcel: 13327001D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05289
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2017 MARTIN BROWN FIRE REVIEW Approved
07/12/2017 GERRY KOZIOL WWM REVIEW Completed
07/17/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the automatic lavatory faucets will dispense a maximum of 0.25 gallons per metering cycle (i.e. what is the maximum cut-off time). Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide backflow protection for all appliances with direct water supply connections. Beverage dispensers (e.g. carbonated beverage dispensers, coffee brewers, etc.) require a backflow prevention device conforming to ASSE 1022. Reference: Sections 608.3 and 608.16.1, IPC 2012.
07/17/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/17/2017 ROBERT SHERRY WATER REVIEW Completed
07/19/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Arby's @ 7920 E. Speedway Blvd.
Interior and Facade remodel.
T17CM05289
Building Plan (1st Review)

TRANSMITTAL DATE: July 19, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Sheet D200 it does not appear that the height dimensions are correctly represented on the plan.

3. Sheet A400 provide height dimensions for all elevations.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
08/01/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A100: Identify location of required accessible seating or Reference Sheet D1.
2. Sheet A000 Code Review: Include calculation for minimum number of plumbing fixtures to be provided. Reference IBC Chapter 29
3. Sheet C101 Drive Thru Canopy: Provide structural calculations for design of foundation for canopy.
4. Sheet A300 Roof Plan: Section 3-A501; verify correct section is referenced for this location.
5. Sheet A501 Wall Section 1: Provide structural calculations for installation of the wall supported canopy at the drive thru window. In addition, add connection details as requiered on drawings.
6. Sheet A501 Wall Section 1: References are made to detail 5/A501 in 2 locations. Detail 5/A501 is denoted as not used. Please verify.
7. Sheet A502 Wall Sections 11, 14 & 16: Include anchorage and bracing information; type, size and spacing of bracing; type, size and number/spacing of fasteners to be used.
8. Sheet A000; Code Review: The total number of occuspans is listed as 84 but the sum of the Dining Room (76) + Kitchen (5) + Restrooms (2) = 83 occupants. Please coordinate.
9. Sheet D3; Section 51: Please indicate the height of the service counter above the finished floor, using ICC ANSI A117.1 Section 904.
10. Sheet A200; Sections 2 & 3: Please indicate connection size & quantity for wood framing members. Reference IBC Table 2304.9.1
11. Sheet A500; Sections 1&3: See note above.
12. General: Provide written responses to all comments.
08/03/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. Can be downloaded from www.tucsonaz.gov/pdsd.