Permit Number: T17CM05287
Parcel: 127122680

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM05287
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Please provide a plan indicating the location of canopies F, F2, F3, F4, and G.
2. Drawing 2; Structural Calculations: The calculations indicate a RT1.5 x 1.5 x ?, while the drawing indicates a 1" x 1" aluminum tube. Please clarify.
3. Drawing 7; Structural Calculations: The calculations indicate a HSS6 x 6 x 1/4, while the drawing indicates a 6" diameter x 0.125" aluminum pipe column. Please clarify.
4. Structural Calculations; Canopy G Foundation: Where is this foundation indicated on the drawings? Please verify.
5. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/13/2018 BLARSON1 OUT TO CUSTOMER Completed