Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM05287
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/05/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Please provide a plan indicating the location of canopies F, F2, F3, F4, and G. 2. Drawing 2; Structural Calculations: The calculations indicate a RT1.5 x 1.5 x ?, while the drawing indicates a 1" x 1" aluminum tube. Please clarify. 3. Drawing 7; Structural Calculations: The calculations indicate a HSS6 x 6 x 1/4, while the drawing indicates a 6" diameter x 0.125" aluminum pipe column. Please clarify. 4. Structural Calculations; Canopy G Foundation: Where is this foundation indicated on the drawings? Please verify. 5. General: Please provide written responses to all review comments. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/13/2018 | BLARSON1 | OUT TO CUSTOMER | Completed |