Permit Number: T17CM05287
Parcel: 127122680

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM05287
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/23/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/29/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A100, Original Comment 1: The note directing to Sheet D1 for location of accessible seating could not be located on Sheet A100. However, the accessible seating was added to Sheet A100 and identified by Delta 1 which also satisfies the original comment.
2. Sheet A501, Original Comment 6: The revision to Wall Section 1 references Wall Section 3/A501. Should this be Detail 3/A502? Verify and revise as necessary.
3. Sheet A502; original Comment 7(partial): Sheet A502 Wall Sections 14 & 16, indicate the type, size and number of fasteners to be used for the bracing.
09/14/2017 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T17CM05287
Building Remodel with Exterior Site Work (1st Review)
5759 E Broadway Boulevard

TRANSMITTAL DATE: September 14, 2017

DUE DATE: Sept 20, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: As noted By Steve shields in the previous building review comments, a DP was required due to proposed site work. The DP was reviewed on August 22, 2017 by Steve Shields. There were corrections that needed to be made to the DP per zoning review comments and as of this building review the DP has not been submitted or presented over the counter for a second zoning review.

At this time zoning cannot approve the building plans until the DP is fully approved.

2. COMMENT: Zoning is willing to review the building plans over the counter on the next submittal assuming that the PDSD Commercial Plans Reviewers approve the building plan. Zoning will require that the DP be approved and presented as reference at the zoning counter in order to verify consistency with the building plans and / or site changes.

3. COMMENT: If the building plans are not approved by the PDSD Commercial Plans Reviewers and a re-submittal is required, zoning will review the building plans on the next submittal.

4. COMMENT: Assure that any changes that are made to the DP site plan that may impact the building (if any), those changes should be made on the building plans before re-submittal.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
09/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Per the last plan review, it was requested to provide compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE for exterior lighting. A reference was also given to access, down load or print the Code for reference. Apparently, the Outdoor Lighting Code was not reviewed, as there is no evidence on the plans for compliance. Please see section 104 of the Code for plan submission requirements. Provide Allowed Lumen vs total proposed lumens for the parcel in acres in reference to table 401.1. Include all necessary information required on the plans as outlined in section 104, to ensure that the proposed exterior lighting including existing, will comply with the Outdoor Lighting Code. The IECC COMCHECK for exterior lighting is not to be confused with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE.