Permit Number: T17CM05287
Parcel: 127122680

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05287
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2017 MARTIN BROWN FIRE REVIEW Approved
07/12/2017 GERRY KOZIOL WWM REVIEW Completed
07/17/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the automatic lavatory faucets will dispense a maximum of 0.25 gallons per metering cycle (i.e. what is the maximum cut-off time). Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide backflow protection for all appliances with direct water supply connections. Beverage dispensers (e.g. carbonated beverage dispensers, coffee brewers, etc.) require a backflow prevention device conforming to ASSE 1022. Reference: Sections 608.3 and 608.16.1, IPC 2012.
3. Vents shall rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Revise the venting of the floor sink located in the seating area. Reference: Section 905.4, IPC 2012.
4. Clarify the proposed fryer model to be installed; the equipment schedule calls for a gas-fired unit but the model number is for an electric unit. Determine the minimum gas pressure for the fryer. Reference: Section 107.2.1, IBC 2012 and Section 402.1, IFGC 2012.
5. Provide calculations to show that the installation of the proposed gas-fired fryer will not cause the existing natural gas distribution piping system to be undersized. Reference: Section 402.1, IFGC 2012.
07/17/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation for the new restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the fans will operate during the hours of operation even if the restroom lights are off). Verify that the flow rate of the air supplied to each restroom is less than or equal to the exhaust flow rate from each restroom. Reference: Section 403.2.1(4), IMC 2012.
07/17/2017 ROBERT SHERRY WATER REVIEW Completed
07/19/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Arby's @ 5759 E. Broadway Blvd
Interior and Facade remodel.
T17CM05287
Building Plan (1st Review)

TRANSMITTAL DATE: July 18, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. As modifications to the site are proposed, i.e. relocation of accessible vehicle parking spaces, accessible ramp modifications, reduction in number of vehicle parking spaces, etc. a Development Package (DP) meeting the requirements of Administrative Manual (AM) 2-06 is required to be submitted and approved prior to approval of the building plans. The DP is a separate submittal that can run concurrently with the building plans. Remove sheets C100 & C101 from the building plans and provide them along with the additional requirements listed below as a DP. A Development Package Checklist has been provided that provides submittal requirement, fees, and PDSD agencies that will need to review the DP. To facilitate a timely review once you have addressed all requirements below email me a pdf of the DP so that I can do a cursory review prior to providing an over-the-counter review of the DP.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956


Administrative Manual 2-06

2-06.3.0 FORMAT REQUIREMENTS

2-06.3.5 - Provide the PDSD Development Package approval stamp in the lower right quadrant of all sheets. The required stamp can be found at http://pdsd.tucsonaz.gov/pdsd/development-permits under Development Package.

2-06.3.7 - A small, project-location map shall be provided in the upper right corner of the cover sheet.

2-06.3.8 - The north arrow, contour interval, and scale as applicable to each sheet should be placed together in the upper right corner of each sheet.

2-06.3.9 - The plan drawing shall be oriented with north toward the top of the sheet. If it is not practical to orient north to the top of the sheet, the plan drawing shall be oriented with north to the left side of the sheet.

2-06.3.10 - A legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

2-06.3.12 - An index of sheets in the development package shall be provided on the first sheet.

2-06.4.0 CONTENT REQUIREMENTS

2-06.4.1 - The name, mailing and email addresses, and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents shall be provided on the right half of the cover sheet. The applicable registration or license number shall be provided if prepared by or with the assistance of a registered professional, such as a surveyor, architect, landscape architect, or engineer. All sealing shall be consistent with Arizona Board of Technical Registration guidelines.

2-06.4.2 - The title block shall include the following information and be provided on each sheet:

2-06.4.2.D - The title block shall include the page number and the total number of pages in the package (i.e., sheet xx of xx).

2-06.4.3 - Provide the development package case number, DP17-0???, adjacent to the title block on all sheets.

2-06.4.3 - Provide the rezoning case number, C9-90-03, adjacent to the title block on all sheets.

2-06.4.4 - The project-location map to be located on the first sheet of the development package in the upper right corner, shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information.

2-06.4.4.A - The project-location map shall show the subject property approximately centered within the one square mile area;

2-06.4.4.B - On the project-location map identify major streets and regional watercourses within the square mile area and all streets that abut the subject property; and,

2-06.4.4.C - Section, township, and range; section corners; north arrow; and the scale will be labeled for the location map.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2-06.4.7.A.1 - List as a general note: "EXISTING ZONING IS C1"

2-06.4.7.A.2 - List the gross area of the site by square footage and acreage.

2-06.4.7.A.4 - Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses. The use should be listed as 'FOOD SERVICE SUBJECT TO USE SPECIFIC STANDARDS 4.9.4.M.1 & 5 and 4.9.13.O".

2-06.4.7.A.5 - On residential projects, list the total number of units/lots proposed.

2-06.4.7.A.6 - Provide a general note on the cover sheet stating "THIS PROJECT IS DESIGNED TO MEET THE OVERLAY ZONE(S) CRITERIA, UDC ARTICLE 5.4 MAJOR STREETS AND ROUTES SETBACK ZONE (MS&R) & UDC ARTICLE 5.5 GATEWAY CORRIDOR ZONE (GCZ) ."

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

2-06.4.8.A - Provide site boundary perimeter information, including bearing in degrees, minutes, and seconds.

2-06.4.8.B - If applicable all easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated.

2-06.4.9.H.5.a - As you propose to remove vehicle parking spaces, plan does not match the approved site plan, vehicle parking space calculation the provides the number of standard spaces required and provided and the number of accessible spaces required and provided.

2-06.4.9.H.5.a - Fully dimension the relocated accessible vehicle parking spaces to include the "C" Space depth, see UDC Article 7.4.6.D and Table 7.4.6-1 and provide a wheel stop location dimension per UDC Article 7.4.6.H.3.

2-06.4.9.H.5.a - Provide a note on the plan stating "PROPOSED ACCESSIBLE VEHICLE PARKING SPACES ARE REQUIRED TO MEET THE REQUIREMENTS OF ICC A117.1-2009 Section 502.5.

2-06.4.9.Q - Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

2-06.4.9.R - Provide a note on the plan stating "ALL PROPOSED PEDESTRIAN ACCESSIBLE ROUTES SLOPES ARE REQUIRED TO MEET THE REQUIREMENTS OF ICC A117.1-2009 Section 403.3.
2-06.4.9.R - Sheet C100 detail 3 it appears that the area between the two striped pedestrian cross walks, high lighted in orange, is flush with pavement. Per TSM Section 7-01.4.2.A Sidewalks associated with PAALs must be physically separated from any vehicular travel lane by means of curbing, grade separation (minimum six inches), barriers, railings, or other means, except at designated crosswalks. That said clearly demonstrate on the plan how this require is met.

2-06.4.9.W - Provide a general note on the plan stating "ALL PROPOSED SIGNAGE REQUIRES SEPARATE PERMIT".
07/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A100: Identify location of required accessible seating or Reference Sheet D1.
2. Sheet A000 Code Review: Include calculation for minimum number of plumbing fixtures to be provided. Reference IBC Chapter 29
3. Sheet C101 Drive Thru Canopy: Provide structural calculations for design of foundation for canopy.
4. Sheet A300 Roof Plan: Section 3-A501; verify correct section is referenced for this location.
5. Sheet A501 Wall Section 1: Provide structural calculations for installation of the wall supported canopy at the drive thru window. In addition, add connection details as required on the plans.
6. Sheet A501 Wall Section 1: References are made to detail 5/A501 in 2 locations. Detail 5/A501 is denoted as not used. Please verify.
7. Sheet A502 Wall Sections 11, 14 & 16: Include anchorage and bracing information; type, size and spacing of bracing; type, size and number/spacing of fasteners to be used.
8. Sheet A000; Code Review: The total number of occuspants is listed as 82 but the sum of the Dining Room (77) + Kitchen (5) + Restrooms (2) = 84 occupants. Please coordinate.
9. Sheet D3; Section 51: Please indicate the height of the service counter above the finished floor, using ICC ANSI A117.1 Section 904.
10. Sheet A200; Sections 2 & 3: Please indicate connection size & quantity for wood framing members. Reference IBC Table 2304.9.1
11. Sheet A500; Sections 1&3: See note above.
12. General: Provide written responses to all comments.
08/02/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. Can be downloaded from www.tucsonaz.gov/pdsd.