Permit Number - T17CM05233
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Upon review of re-submittal it was noticed there are revisions identified as Delta 2 Site Revisions. Please provide explanation of revisions including sheet number for which they occur.
2. Provide a Special Inspection Certificate which has been signed by the Owner or Legal Agent. Also, provide the inspector's name for each category of required special inspection.
08/21/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Remove the additional keynote #13 located in the new restroom (room 105).
08/21/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The resubmitted drawing still references a discontinued and unlisted mixing valve. [Initial comment: Provide tempered water (85 - 110 degrees Fahrenheit) for the public restroom lavatory using an approved device conforming to ASSE 1070. Watts has discontinued the model L111 thermostatic mixing valve. Reference: Sections 416.5 and 607.1.2, IPC 2012.]