Permit Number: T17CM05233
Parcel: 13317062A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05233
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Correct the expiration date for the engineer's seal. Reference: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration
2. Provide tempered water (85 - 110 degrees Fahrenheit) for the public restroom lavatory using an approved device conforming to ASSE 1070. Watts has discontinued the model L111 thermostatic mixing valve. Reference: Sections 416.5 and 607.1.2, IPC 2012.
07/11/2017 ROBERT SHERRY WATER REVIEW Completed
07/11/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide heating and cooling load calculations that justify the capacity of FC-1. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012
3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to the restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
4. Revise the mechanical design for FC-1 as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
07/20/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/28/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/15/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-100; Plumbing Fixtures (Drinking Fountain): The drawing indicates a water cooler may be substituted for a drinking fountain per the IPC Section 410.3. This section indicates water coolers or bottled water dispensers may be substituted for not more than 50% of the required number of drinking fountains. Is there an existing high/low drinking fountain, or a single point of use dispenser, currently in use? Please verify.
2. Sheet A-100; Project Code Analysis: The drawing indicates this project is a tenant improvement in an existing shell building. Is that correct?
3. Sheet A-210; Floor Plan General Notes: Note F indicates all partitions to be Type 1A unless noted otherwise. The floor plan also indicates 2A and 2B partitions. Please add a note on this sheet to reference the partition schedule and partition general notes on Sheet A-801.
4. Sheet E-300; Lighting Plan: Should there be a directional exit sign indicated on this plan in the hall and at the exit? With the hall configuration, it might help direct occupants to the exit door 107 from hall 101. Please verify.
5. General: Please provide written responses to all review comments.