Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM05147
Parcel: 12709005A

Address:
5550 E 5TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM05147
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide inverter cut sheets or specs.
#2. Indicate wiring methods on the plans to show how the proposed lighting will utilize the existing lighting branch circuits. Also indicate devices for switching, j-boxes, conduit, conductors, sizes and types used to perform the installation of the luminaires.
Ref: 2012 IBC 107.2.1, 2011 NEC