Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM05147
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide inverter cut sheets or specs. #2. Indicate wiring methods on the plans to show how the proposed lighting will utilize the existing lighting branch circuits. Also indicate devices for switching, j-boxes, conduit, conductors, sizes and types used to perform the installation of the luminaires. Ref: 2012 IBC 107.2.1, 2011 NEC |