Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM05147
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet PV1.0 (System Description); Sheet PV1.1 (Array Plans P1 and P2): Sheet PV1.0 indicates array P1 has an area of 5590 SF and array P2 has an area of 3633 SF for a total of 9223 SF. Sheet PV1.1 indicates array P1 is 167'-9" long x 34'-0" wide (5704 SF), and array P2 is 181'-9" long x 20'-5" wide (3712 SF) for a total of 9416 SF. Please coordinate.
2. Structural Calculations (P1); Beam Design: The three beam designs indicated in the calculations are for a 24' span with an 8' cantilever, a 26.25' span with an 8.75' cantilever, and another 26.25' span with an 8.75' cantilever. Please revise.
3. Structural Calculations (P1); Beam/Column Design: The length of beam M1 on SK-1 indicates 32.416', and the length of the column M2 indicates 11.297'. Please verify the member sizes using revised lengths.
4. Structural Calculations (P2); Beam/Column Design: See Comment 3 for member sizes. Please verify.
5. General: Please provide written responses to all review comments.
07/31/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2017 KROBLES1 OUT TO CUSTOMER Completed