Permit Review Detail
Review Status: Active
Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Permit Number - T17CM05139
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2017 | ANDREW CONNOR | ZONING | REVIEW | Reqs Change | COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1). This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). The applicant has built a 16' 6" two-story addition to existing structure with a 0' setback to the West property line. The required setback would be 10.89' |
| 07/03/2017 | ANY | BUILDING-RESIDENTIAL | REVIEW | Active | |
| 07/03/2017 | ANY | ENGINEERING | REVIEW | Active |