Permit Number: T17CM05096
Parcel: 140292080

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05096
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2017 ANDREW CONNOR ZONING REVIEW Approved
06/30/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the "free air returns" noted in drawing M102 penetrate the fire-rated partitions.
06/30/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/30/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/30/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Plans and notes provide minimal information. Please include information such as; locations of and required fire rating of partitions, doors and other penetrations. Update door schedule as necessary to reflect required fire rating.
2. As submitted, it appears there are several new small wall partions being installed (near various doors), please clarify and identify wall type as necessary.
3. Note: additional comments may be forthcoming once revised plans are reviewed.
4. Sheet A320. Provide detail for bracing of Partition Type 1, include type and size of bracing material; type, size and number of fasteners to be used.
5. Provide written responses to all comments.
06/30/2017 ROBERT SHERRY WATER REVIEW Completed
06/30/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/30/2017 JVINCEN1 FIRE REVIEW Approved
06/30/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/30/2017 RSHERRY1 WWM REVIEW Passed No Plumbing