Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05096
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 06/30/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how the "free air returns" noted in drawing M102 penetrate the fire-rated partitions. |
| 06/30/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/30/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 06/30/2017 | TPROBAS1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Plans and notes provide minimal information. Please include information such as; locations of and required fire rating of partitions, doors and other penetrations. Update door schedule as necessary to reflect required fire rating. 2. As submitted, it appears there are several new small wall partions being installed (near various doors), please clarify and identify wall type as necessary. 3. Note: additional comments may be forthcoming once revised plans are reviewed. 4. Sheet A320. Provide detail for bracing of Partition Type 1, include type and size of bracing material; type, size and number of fasteners to be used. 5. Provide written responses to all comments. |
| 06/30/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/30/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/30/2017 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 06/30/2017 | TPROBAS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/30/2017 | RSHERRY1 | WWM | REVIEW | Passed | No Plumbing |