Permit Number: T17CM05091
Parcel: 115160460

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05091
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2017 RSHERRY1 WWM REVIEW Passed No Plumbing
06/30/2017 ROBERT SHERRY WATER REVIEW Completed
06/30/2017 JVINCEN1 FIRE REVIEW Approved
06/30/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/30/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/30/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/30/2017 ACONNOR1 ENGINEERING REVIEW Approved
06/30/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/30/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Occupancy group for sales should be Group M.
2. As proposed, plans indicate possible separated occupancy. M/S-2 would require a 1 hr separation. If non separated, please indicate such on code review.
3. Group M occupancy requires 2 exits with an occupant load greater than 49. Cannont exit through interveining S-2 space as it is a higher hazard class than M. IBC 1014.2
Provide elevation for sales counter which complies with ADA.
06/30/2017 ANDREW CONNOR ZONING REVIEW Approved