Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM05090
Parcel: 115044540

Address:
1135 N PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM05090
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change T17CM05090 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, July 6, 2017
MECHANICAL – COMMERCIAL
Exhaust Fan Schedule on sheet M1 marks the new fan as EF-4 serving kitchen hood KH-2. Is this correct? The plan shows the new fan as EF-1 serving new kitchen hood KH-1. Please explain. Ref. 2012 IMC 106.3.1.
Submit structural calculations sealed by an Arizona registrant showing that existing roof framing will support new 675-lb kitchen hood in location shown. Ref. 2012 IBC 107.2.1.
Heating and cooling load calculations were submitted with this project however no new heat pumps are shown on any of the mechanical plans or schedules. Please explain.
07/07/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Revise note on Site Plan, sheet A1, from “Existing 5/8” water meter” to “New ¾” water meter.”
Either provide a scaled civil site plan showing extents, routing and locations of existing and new site utilities or clearly add this information to the (unscaled) Site Plan on sheet A1. If use the Site Plan on sheet A1 provide total lengths of new sanitary and water piping to the plan. The Plumbing Waste Floor Plan on sheet P1 shows a new sanitary lines connecting to an existing 4” sewer. Is this existing 4” sewer public or private? Show it on a site plan and how/where it connects to the public sewer.
On Plumbing Waste Floor Plan, sheet P1, the connection for the new hand sink seems to be incorrectly labeled. Is there a 3” GW to (E) 4” S in this location that the new 2” hand sink sanitary will connect to?
Add a note to new hand sink 48 that a sign stating “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED” shall be posted above the sink. Ref. City of Tucson amendment to 2012 IPC 1003.3 (A), sub note 3.
The plumbing plan on sheet P2 is incorrectly labeled. This should be Plumbing Gas Floor Plan rather than Plumbing Demo Floor Plan.