Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM05087
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/08/2017 | TPROBAS1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet C1: Exterior patio area shall be included in the occupant load calculations. IBC 1004.5 2. Wall by cooler is denoted on Sheet A2 as existing but other sheets it is denoted as new. Verify and cooridinate. 3. Sheet A3: Include on the drawings restroom details which coincide with ANSI A117.1-2009 Figures 604.3, 604.5.1 & 604.5.2. (mens restroom does not comply as submitted) 4. Sheet A5 Keynotes: Keynote 6 denotes grab bar to be 12", must be 18". ANSI A117.1-2009 Chapter 6 5. Provide structural calculations. 6. Include on the drawings a detail for the fence and gates. 7. General: Include written responses for all comments. |
| 11/08/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/14/2017 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 11/14/2017 | QJONES1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/14/2017 | QJONES1 | FIRE | REVIEW | Needs Review | |
| 11/14/2017 | QJONES1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/14/2017 | QJONES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/14/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 11/14/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 11/14/2017 | QJONES1 | REJECT SHELF | Completed |