Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM04944
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/06/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/06/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Specify the required maximum NFRC-certified U-factors and Solar Heat Gain Coefficients (SHGC) for the new storefront on the architectural drawings. Reference: Sections C103.2 C303.1.3, and C402.3.3, IECC 2012. 2. Verify that the materials used within the return air plenum are non-combustible or have a flame-spread index of 25 or less and a smoke-developed rating of 50 or less. Reference: Section 602.2.1, IMC 2012. |
| 07/12/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet T2.0 Life Safety Plan: Door 5 does not swing in the direction of egress. Doors shall swing in the direction of egress when serving a space containing an occupant load of 50 or more persons. Reference IBC 1008.1.2 2. Sheet G1.1 Water Closet Details: Provide vertical grab bar in accordance with ANSI A117.1 Section 604.5.1. 3. Please provide structural calculations to support the installation of the new rooftop units. In lieu of calculations, information regarding the existing units may be provided to verify weight of new units does not exceed weight of new units. 4. Please provide a Special Inspection Certificate for field welding, epoxy dowels and expansion anchors. 5. General: Provide written responses for all comments. |
| 07/20/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |