Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM04938
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/07/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Connection of potable water to an appliance (e.g. ice machine) requires the use of a backflow prevention method identified in Table 608.1 or Sections 608.13.1 through 608.13.9, IPC 2012. 2. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. |
07/07/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Condensate from the Type II exhaust duct may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (e.g. onto a sidewalk as noted in detail 1/M2.0). Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. 2. Type II exhaust systems shall be independent of all other exhaust systems (e.g. environmental air exhaust). Reference; Section 501.2, IMC 2012. 3. Show how the proposed termination of the Type II exhaust duct complies with requirements (2) and (7) of Section 506.4.2, IMC 2012 (i.e. 10-feet from property line and not directed onto a walkway). 4. Specify how the positively pressurized exhaust duct is to be sealed. Reference: Sections 506.4.1 and 603.9, IMC 2012. |
07/07/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
07/13/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 1.0 Code Review: Please include the calculation for required accessible seating and indicate location on the plans. 2. Sheet 2.0 Floor Plan Wall Legend: Wall W-2 is denoted as 2x4 framing. Sheet S1.0 Code Review denotes the construction type as II-B, non-combustible. New walls would need to be of non-combustible construction to maintain the II-B construction type. Please clarify and revise as necessary. Reference IBC Section 602 for construction types. 3. Sheet 2.0 Floor Plan: Wall W-2 is indicated as 2x4 framing while dimensioning is denoted as 5 ¼". Please clarify and revise as necessary. 4. Sheet 2.0 Floor Plan: Please provide a wall detail for Wall W-2. Include framing material, spacing, anchoring/attachment to structure, finish material, bracing with type, size and number of fasteners to be used, etc. 5. Sheet 2.0 Floor Plan General Notes: Please remove notes which reference the restrooms as there is no indication of the restrooms being in the scope of work. 6. Sheet 2.0 Floor Plan: In the NE portion of the building there is a note "existing 5' 5 ½". Please indicate what is existing. 7. Sheet 4.0 Exterior Elevations Detail 2a: Please indicate the type, size and number/spacing of fasteners to be used for the sign attachment. 8. General: Provide written responses to all comments. |
07/20/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |