Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM04736
Parcel: 11207168A

Address:
2501 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM04736
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2017 DAVID RIVERA ADA REVIEW Passed
06/20/2017 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T17CM04736
Building Plan Review (1st Review)
2501 E. Grant Road (Food Service / Commercial Recreation-Athletic Club)

TRANSMITTAL DATE: June 20, 2017

DUE DATE: July 14, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package DP16-0235. While the building footprint is consistent with the current version of the PDSD approved DP as it relates to the zoning review purview (Use(s), Building footprint, Height, Building square footage, Site conditions etc) zoning cannot approve the building plans until the Commercial Plans reviewers have approved the building plans and a revised Development Package has been fully approved by PDSD.

(As of this review of the building plans by zoning, the plan review by the PDSD commercial plans review agencies has not been completed. Zoning cannot approve the building plans until all commercial review agencies have approved and signed the building plans.)

2. COMMENT: Assure that an approved and signed copy of the DP is included in the next submittal of the building plans or remove the DP plan set from the building plans set and reference the DP case number on the Architectural site plan.

3. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements and that the above comments have been addressed.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email, David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
06/21/2017 MARTIN BROWN FIRE REVIEW Approved
06/26/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS: Site data references Maricopa County. Please revise.
2. Sheet TS: Occupancy Information Required Exit Width references Building Code Study. Required Exit Width was not provided.
3. Sheet TS: The City of Tucson requires all lettering, upper and lower case, to be a minimum 3/32" in height. Comment typical all plan sheets as applicable.
4. Sheet TS: Occupancy Information Building Area indicates an allowable area of 24,000 sq. ft. per 2012 IBC Section 503. In accordance with IBC Section 503, specifically Table 503, an A-2 Occupancy with VB construction is limited to 6,000 sq. ft. It is assumed the additional 18,000 sq. ft. is due to an area increase for Automatic Fire System. Please indicate the area increase on the plans. (6,000 allowable + 18,000 increase for sprinkler =24,000 total allowable)
5. Sheet S0.1: Expansion Anchors in Concrete, Simpson Strong Bolt Report #2322 is no longer valid. Please reference a current report.
6. Sheet S0.1: Epoxy Anchors in Concrete, Hilti HIT RE-500-SD Report 2322 is no longer valid. Please reference a current report.
7. Sheet S0.1: Deferred Submittals references 2006 IBC. Please revise to reference 2012 IBC.
8. Sheet S0.1: Special Inspection Table denoted in Special Inspections could not be found.
9. Provide a special inspection certificate.
10. General: Provide written responses to all comments.
06/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the location of the existing water meter and water service as shown on the civil utility drawing (5 of 15) with the plumbing plan, P1.1. Reference: Section 107.2.1, IBC 2012.
06/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the maximum gas input to the rooftop units, AC-1, 2, 3, and 4. The minimum heating capacity appears to be about 28-34% higher than the maximum gas input. Reference: Section 107.2.1, IBC 2012.
06/28/2017 ROBERT SHERRY WATER REVIEW Completed
07/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Correct references to 2012 NEC. Should be 2011.
#2. Provide illumination for the electric room. NEC 110.26D
#3. The panel schedules are not readable due to light printing.
#4. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. Can be downloaded at www.tucsonaz.gov/pdsd. See section 104, Plan Submittal Requirements.
Ref : 2012 IBC 107.2.1, 2011 NEC, TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE.
07/17/2017 LOREN MAKUS ENGINEERING REVIEW Approved
07/20/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/20/2017 GERRY KOZIOL WWM REVIEW Reqs Change Need for Sewer Connection Fee Application Approval:



PCRWRD/IWC/ Steven Valencia review & approval for installation of 2000 gallon grease interceptor per DP and plumbing drawing P1.1 (520-724-6200 - steven.valencia@pima.gov).

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2017 KROBLES1 OUT TO CUSTOMER Completed