Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM04663
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/30/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide 100 CFM of exhaust to the outside for the hood in the teaching kitchen unless mechanical ventilation is otherwise provided. Reference: Sections 202, 403.3, and 507.2.2, IMC 2012. 2. Provide exhaust for the copy room. Reference: Section 403.3, IMC 2012. |
| 06/30/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/05/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the roof drain calculations to include the effect of any vertical walls that can divert rainfall onto the roof. Reference: Section 1106.4, IPC 2012. |
| 07/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.1: Overlapping keynotes at gridline 3B. Please revise. 2. Sheet A1.1: Door 120A blocks egress path at Door 111A. 3. Sheet A1.1: Separate restroom facilities are required for each sex, however; a shower is only being provided in Restroom 2. Please identify Restrooms in accordance with IBC 2902.2.1. 4. Sheet A5.5: Detail 3 calls out Detail 7 of Sheet A5.4 on the handrail. Detail 7/A5.4 is Stairs-Typical Edge Detail. Please revise. 5. Sheet S0.1 Expansion Bolts in Concrete: Simpson Strong Bolt Report 1771 is no longer valid. Please reference a current report. 6. Sheet S0.1 Epoxy Bolts in Concrete: Hilti-RE 500 SD Report 2322 is no longer valid. Please reference a current report. 7. Sheet S0.1 Epoxy Bolts in CMU: Hilti HIT-HY 150 Report 2678 is no longer valid. Please reference a current report. 8. Sheet S0.1 Epoxy Bolts in CMU: Hilti HIT-HY 150 Max Report 1967 is no longer valid. Please reference a current report. 9. Sheet S0.1 Epoxy Bolts in CMU: Powers Powers-Fast+ Standard Set Report 1531 is no longer valid. Please reference a current report. 10. Sheet S0.1 Epoxy Bolts in Brick: Powers-Fast+ Standard Set Report1617 is no longer valid. Please reference a current report. 11. Sheet S0.1 Shot Pins in Concrete: Powers Trak-It C4 Report 2249 is no longer valid. Please reference a current report. 12. Sheet S0.2: Please provide a Special Inspection Certificate for all Required Special Inspections denoted. 13. General: Provide written responses to all comments. |
| 07/12/2017 | TPROBAS1 | ADA | REVIEW | Passed | |
| 07/17/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |