Permit Number: T17CM04663
Parcel: 11704310B

Address:
526 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04663
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2017 MARTIN BROWN FIRE REVIEW Approved
06/30/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide 100 CFM of exhaust to the outside for the hood in the teaching kitchen unless mechanical ventilation is otherwise provided. Reference: Sections 202, 403.3, and 507.2.2, IMC 2012.
2. Provide exhaust for the copy room. Reference: Section 403.3, IMC 2012.
06/30/2017 ROBERT SHERRY WATER REVIEW Completed
07/05/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the roof drain calculations to include the effect of any vertical walls that can divert rainfall onto the roof. Reference: Section 1106.4, IPC 2012.
07/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.1: Overlapping keynotes at gridline 3B. Please revise.
2. Sheet A1.1: Door 120A blocks egress path at Door 111A.
3. Sheet A1.1: Separate restroom facilities are required for each sex, however; a shower is only being provided in Restroom 2. Please identify Restrooms in accordance with IBC 2902.2.1.
4. Sheet A5.5: Detail 3 calls out Detail 7 of Sheet A5.4 on the handrail. Detail 7/A5.4 is Stairs-Typical Edge Detail. Please revise.
5. Sheet S0.1 Expansion Bolts in Concrete: Simpson Strong Bolt Report 1771 is no longer valid. Please reference a current report.
6. Sheet S0.1 Epoxy Bolts in Concrete: Hilti-RE 500 SD Report 2322 is no longer valid. Please reference a current report.
7. Sheet S0.1 Epoxy Bolts in CMU: Hilti HIT-HY 150 Report 2678 is no longer valid. Please reference a current report.
8. Sheet S0.1 Epoxy Bolts in CMU: Hilti HIT-HY 150 Max Report 1967 is no longer valid. Please reference a current report.
9. Sheet S0.1 Epoxy Bolts in CMU: Powers Powers-Fast+ Standard Set Report 1531 is no longer valid. Please reference a current report.
10. Sheet S0.1 Epoxy Bolts in Brick: Powers-Fast+ Standard Set Report1617 is no longer valid. Please reference a current report.
11. Sheet S0.1 Shot Pins in Concrete: Powers Trak-It C4 Report 2249 is no longer valid. Please reference a current report.
12. Sheet S0.2: Please provide a Special Inspection Certificate for all Required Special Inspections denoted.
13. General: Provide written responses to all comments.
07/12/2017 TPROBAS1 ADA REVIEW Passed
07/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved