Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM04657
Parcel: 12618127B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04657
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2017 ANDREW CONNOR ZONING REVIEW Approved
06/15/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/15/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Please clarify keynote #2, plan sheet E2.0 Power plan, points to panel.
#2. Please locate the mechanical equipment and disconnects on the electrical floor plans.
#3. The electrical panel schedule shows the water heater on a 120 volt branch circuit, however the plumbing plan shows it rated at 208 volts.
Ref 2012 IBC 107.2.1, 2011 NEC.
06/15/2017 MARTIN BROWN FIRE REVIEW Approved
06/16/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/16/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/16/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a 4" cleanout for the existing 4" sewer serving the new clotheswasher.
06/16/2017 ROBERT SHERRY WATER REVIEW Completed
06/16/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/22/2017 GERRY KOZIOL WWM REVIEW Completed