Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM04657
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/15/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 06/15/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 06/15/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Please clarify keynote #2, plan sheet E2.0 Power plan, points to panel. #2. Please locate the mechanical equipment and disconnects on the electrical floor plans. #3. The electrical panel schedule shows the water heater on a 120 volt branch circuit, however the plumbing plan shows it rated at 208 volts. Ref 2012 IBC 107.2.1, 2011 NEC. |
| 06/15/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/16/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/16/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/16/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a 4" cleanout for the existing 4" sewer serving the new clotheswasher. |
| 06/16/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/16/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 06/22/2017 | GERRY KOZIOL | WWM | REVIEW | Completed |