Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM04648
Parcel: 135074550

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04648
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2017 ANDREW CONNOR ZONING REVIEW Approved
06/15/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/15/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/15/2017 MARTIN BROWN FIRE REVIEW Approved
06/15/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
06/26/2017 ROBERT SHERRY WATER REVIEW Completed
06/26/2017 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Completed
06/26/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Completed 1. Restroom cannot open directly into area for food prep.
2. Provide detail for new wall to be added for restroom compliance.
07/03/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed PRovide general exhaust for the two convection ovens at a rate of 70 CFM per oven. Reference: Section 507.2.2, IMC 2012.
07/03/2017 GERRY KOZIOL WWM REVIEW Completed