Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T17CM04646
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. #1. The panel schedule for panel L1 does not show the Circuit breaker or location on the bus for Panel L2 OCPD. #2. Where and how does the feeder for the Brew House tie in to the existing electrical system? Indicate wiring methods on the plan. Ref: 2012 IBC 107.2.1, 2011 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/14/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 09/14/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 09/14/2017 | QJONES1 | REJECT SHELF | Completed |