09/12/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. The panel schedule for panel L1 does not show the Circuit breaker or location on the bus for Panel L2 OCPD.
#2. Where and how does the feeder for the Brew House tie in to the existing electrical system? Indicate wiring methods on the plan.
Ref: 2012 IBC 107.2.1, 2011 NEC.