Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM04612
Parcel: 124071390

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T17CM04612
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2017 ROBERT SHERRY WATER REVIEW Reqs Change Tucson Water limits 4" water meters to maximum demand of 475-GPM. Provide the demand that the proposed water meter will serve to show that the demand will not exceed the allowable limit. Reference: Section 107.2.1, IBC 2012.
07/31/2017 MARTIN BROWN FIRE REVIEW Approv-Cond Contingent on 3rd party approval
07/31/2017 LOREN MAKUS ENGINEERING REVIEW Approved
08/04/2017 GERRY KOZIOL WWM REVIEW Reqs Change The following is needed for Sewer Connection Fee Application Approval:

Need to review Water Meter size per City of Tucson (4” may not be adequate).

Need PCRWRD/IWC review of sand/oil interceptor for underground parking area drains (Steven.valencia@pima.gov – 520-724-6200).
08/04/2017 KELLY LEE ZONING REVIEW Reqs Change FROM: Kelly Lee
PDSD Zoning Review Section

PROJECT: T17CM04612
Building Plan Review (1st Review)
999 E Broadway - New Apartment Complex (Multi-Family)

TRANSMITTAL DATE: August 3, 2017

DUE DATE: August 3, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the development package. While the building footprint and the site revisions are consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the Commercial Plans reviewers have approved the building plans.

2. COMMENT: The DP included in the current building plan submittal is not the approved plan set as it has not been signed. Please include the signed plan set in the next submittal of the building plans.

3. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements.

4. Prior to Building Plan issuance, the recordation of the Covenant regarding Development and Use of Real Property must be provided to PDSD.

If you have any questions about this transmittal, Contact Kelly Lee at (520) 837-6999 or by email Kelly.Lee@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised building plans
************************************************************************
08/04/2017 KLEE1 ZONING HC REVIEW Reqs Change See Zoning Comments.
08/15/2017 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Needs Review
08/15/2017 ARUIZ1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2017 ARUIZ1 OUT TO CUSTOMER Completed