Permit Number: T17CM04543
Parcel: 133400020

Address:
555 N PANTANO RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04543
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2017 ANDREW CONNOR ZONING REVIEW Approved
06/14/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/22/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/22/2017 TPROBAS1 MECHANICAL-COMMERCIAL REVIEW Completed
06/22/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Occupant load shall be at a rate of 1/15 for assembly, unconcentrated.
2. Sheet A2.01 references detail 13/A4.03. There is no sheet A4.03.
3. Provide an attachment detail for the firred walls to masonry.
4. Provide an elevation drawing of the counters which complies with ADA for at least one space.
5. Structural to evaluate the existing roof for the new Rooftop unit and provide detail.
6. Need special inspection certificate for masonry and field welding (optional lintel).
06/22/2017 MARTIN BROWN FIRE REVIEW Reqs Change Please review section 1008.1.10 of the 2012 International Fire Code for panic hardware. Revise plans accordingly.
It appears door width calculations are based on a sprinklered building. Please review.
06/22/2017 TPROBAS1 PLUMBING-COMMERCIAL REVIEW Completed
06/22/2017 TPROBAS1 WATER REVIEW Passed
06/27/2017 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/27/2017 GERRY KOZIOL WWM REVIEW Completed