Permit Number: T17CM04539
Parcel: 13413057D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04539
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2017 ANDREW CONNOR ZONING REVIEW Approved
06/12/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/12/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified lavatory faucets will be set to dispense a maximum of 0.25 gallons per metering cycle. The dispensing cycle shall last for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
06/12/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/12/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/12/2017 ROBERT SHERRY WATER REVIEW Completed
06/12/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/13/2017 MARTIN BROWN FIRE REVIEW Approved
06/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the 2012 IECC for the lighting.
06/14/2017 GERRY KOZIOL WWM REVIEW Completed