Permit Number: T17CM04472
Parcel: 13215024A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM04472
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Reqs Change Sheet A1.1: please identify each restroom as applicable; mens, womens or unisex.
2. Sheet A1.0 Wall type B references detail 2 A/1.0. Should this be 2 A/2.0?
Sheet A2.0 original comment 13: no change. Electrical and Architectural floor plans do not match.
07/18/2017 AMORALE3 FIRE REVIEW Reqs Change
07/18/2017 AMORALE3 PLUMBING-COMMERCIAL REVIEW Reqs Change