Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM04472
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/08/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
06/08/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
06/08/2017 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
06/08/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
06/08/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
06/08/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
06/08/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
06/08/2017 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1) Note on cover sheet indicates no sprinklers. Mechanical sheet indicates a sprinkler system. Please clarify. 2) Please review section 105.6.8. of the 2012 IFC. Then express quantities of gases in terms of allowable amounts per this section. If amounts are exceeded, review section 5306 for requirements of med gas storage rooms. 3) Please indicate if a fire alarm system is intented. |
06/12/2017 | ARUIZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
06/12/2017 | ARUIZ1 | WWM | REVIEW | Completed |