Permit Number: T17CM04472
Parcel: 13215024A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04472
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2017 ANDREW CONNOR ZONING REVIEW Approved
06/08/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/08/2017 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/08/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/08/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
06/08/2017 ROBERT SHERRY WATER REVIEW Completed
06/08/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
06/08/2017 MARTIN BROWN FIRE REVIEW Reqs Change 1) Note on cover sheet indicates no sprinklers. Mechanical sheet indicates a sprinkler system. Please clarify.
2) Please review section 105.6.8. of the 2012 IFC. Then express quantities of gases in terms of allowable amounts per this section. If amounts are exceeded, review section 5306 for requirements of med gas storage rooms.
3) Please indicate if a fire alarm system is intented.
06/12/2017 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
06/12/2017 ARUIZ1 WWM REVIEW Completed