Permit Number: T17CM04471
Parcel: 11515129A

Address:
601 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM04471
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2017 MARTIN BROWN FIRE REVIEW Approved
07/11/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/12/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Plan sheets PP1.1 through PP3.1 show a total of 4 pumps, one for each tank. The electrical plans only show 3. Please clarify.
#2. Provide a complete panel schedule for panel 'C'.
#3. Indicate new or existing for the service and associated equipment.
#4. Ref: plan sheet E1.1. Keyed note #5. Please identify this panel and locate on the electrical power plan.
#5. Identify all the pumps on the power plan.
#6. Indicate conduit, conductor, types and sizes for all the pump circuits.
Ref: 2012 IBC 107.2.1, 2011 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2017 ARUIZ1 OUT TO CUSTOMER Completed