Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM04471
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/13/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/11/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/12/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Plan sheets PP1.1 through PP3.1 show a total of 4 pumps, one for each tank. The electrical plans only show 3. Please clarify. #2. Provide a complete panel schedule for panel 'C'. #3. Indicate new or existing for the service and associated equipment. #4. Ref: plan sheet E1.1. Keyed note #5. Please identify this panel and locate on the electrical power plan. #5. Identify all the pumps on the power plan. #6. Indicate conduit, conductor, types and sizes for all the pump circuits. Ref: 2012 IBC 107.2.1, 2011 NEC. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/26/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |