Permit Number: T17CM04454
Parcel: 14042023C

Address:
2929 E CORONA RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM04454
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2017 LOREN MAKUS ENGINEERING REVIEW Passed
06/07/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/30/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Alorica
T17CM04454
Building Plan (1st Review)

TRANSMITTAL DATE: June 30, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. As vehicle parking is being removed for placement of the generator provide an updated vehicle parking space calculation.

3. Sheet E1.1 shows the generator in a different location than sheet S1.1, clarify which is correct.

4. Sheet E1.1 shows the generator directly adjacent to the vehicle parking space to the south. Per UDC Article 7.4.6.D.2.b Minimum Width Requirement When Adjacent to Barrie A motor vehicle off-street parking space must have a minimum width of ten feet when the side(s) of the parking space abuts a vertical barrier over six inches in height, other than a vertical support for a carport. Demonstrate that the vehicle parking space meets the above requirements.

5. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
07/11/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.1: Sheet is labeled Not For Construction. Please revise.
2. Sheet S1.1: Registrant seal is is covered with text and is not legible. Registrant seal must be legible.
3. Sheet S1.1: HIT RE 500 Adhesive Anchor Report #2322 is no longer valid. Please provide valid report.
4. HIT 150 MAX SD Report #3013 is no longer valid. Please provide a valid report.
5. General: Please provide a special inspection certificate for all required Special Inspections.
6. Provide structural calculations for foundation.
7. General: Provide written responses for all comments.
08/04/2017 MARTIN BROWN FIRE REVIEW Approved Please provide mnfgf's cut sheets for generator. Clarify if diesel is self contyained within the unit, or a separate containment tank for the fuel is required.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2017 KROBLES1 OUT TO CUSTOMER Completed