Permit Number: T17CM04391
Parcel: 12310001A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM04391
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/06/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Complete drawings -see markups
10/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1 Ref: Plan Sheet M701 and E121. The electrical floor plan shows 5 motor rated toggle switches for terminal units, and the mechanical plan calls for 9 units per the Terminal Unit Schedule. Please clarify.
Ref: 2012 IBC sec, 107.2.1, 2011 NEC
10/19/2017 TWEIDEM1 FIRE REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/03/2017 FERNE RODRIGUEZ OUT TO CUSTOMER Completed