Permit Number: T17CM04391
Parcel: 12310001A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04391
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2017 STEVE SHIELDS ZONING REVIEW Approved
06/12/2017 SSHIELD1 ENGINEERING REVIEW Passed
06/12/2017 MARTIN BROWN FIRE REVIEW Approved
06/16/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify that the automatic time out settings for the lavatory faucets are set to deliver no more than 0.25 gallons per cycle. Each cycle shall last for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Verify that the temperature mixing valves for the lavatory faucets are listed to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
06/16/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/16/2017 ROBERT SHERRY WATER REVIEW Completed
06/28/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide provisions for a sign or warning label for the new Critical Panel RIC-20
As required per 2011 NEC art. 700.10
07/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet AD101; Demolition Plan: Keynotes 8 and 10 were not located on the plan. Please verify.
2. Sheet A503; Detail 1: The 2x8 wood joists indicate spacing at 18" o.c. Is this spacing correct?
3. Sheet A503; Detail 3: Please indicate the number and size of connectors at the diagonal bracing to the vertical studs.
4. Sheet A503; Detail 3: Please extend the detail to indicate the diagonal bracing and vertical studs to the structure above, including connector information as required.
5. General: Please provide written responses to all review comments.
07/06/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/31/2017 CTREVIL1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2017 TWEIDEM1 APPROVAL SHELF Completed
07/31/2017 TWEIDEM1 OUT TO CUSTOMER Completed
07/31/2017 TWEIDEM1 REJECT SHELF Completed