Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM04357
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2017 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/01/2017 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | T17CM04357/64– PLAN REVIEW COMMENTS - 2nd Review Reviewer: Chris Anderson, July 31, 2017 PLUMBING – COMMERCIAL On sheet P1.2 two 6” building drains connect to a 4” BCS (shown on utility plan) which connects to the existing 8” sewer under W. Sahuaro Street. The size of drainage piping shall not be reduced in the direction of flow. Either reduce the size of the two building drain lines to 4” or enlarge the building sewer to 6” and provide a manhole where connects to the 8” public sewer. Ref. 2012 IPC 704.2 and 2016 RWRD Engineering Design Standard 5.3.2. |
| 08/01/2017 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/01/2017 | FRODRIG2 | WWM | REVIEW | Reqs Change | WASTEWATER – COMMERCIAL A Type III Capacity from PCRWRD/RWRDCapacityResponse@pima.gov is needed for Sewer Connection Fee Application approval. |
| 08/01/2017 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/01/2017 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/11/2017 | ANELSON2 | APPROVAL SHELF | Completed |
| 08/11/2017 | ANELSON2 | OUT TO CUSTOMER | Completed |
| 08/11/2017 | ANELSON2 | REJECT SHELF | Completed |