Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM04319
Parcel: 11108470B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04319
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change BUILDING – COMMERCIAL
Reviewer: Charlie Bard, June 16, 2017

Original plans for this project calls out a 1 Hr. fire partition wall at the entry wall to all units. Provide documentation the new doors have a 20 minute fire rating per Table 716.5.
06/19/2017 FRODRIG2 WATER REVIEW Approved
06/19/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Approved
06/19/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL - COMMERCIAL
Reviewer: Charlie Bard, June 16, 2017

Original plans called out gas water heater and range at each unit, show new circuits on electric plan for the water heater and range. Page A-1
Add note to plan it if these unites have fuel fired appliances:
Where work requiring a permit occurs in existing dwellings that have attached garages or in existing dwellings within which fuel-fired appliances exist, carbon monoxide alarms shall be provided in accordance with Section R315.
Add note:
Where branch-circuit wiring is modified replaced or extended in any of the areas specified in section E3902.12 the branch circuit shall be protected by one of the following. A combination-type AFCI or an outlet branch-circuit type AFCI at the first outlet.
Provide plan showing exterior lighting that is being replaced and provide an Outdoor Lighting Code Calculation/note for compliance. (Note lighting color temp. for full cut off lighting maximum is 3500K and unshielded 3000K.
Add note:
E3905.8 Boxes at fan outlets.
Outlet boxes and outlet box systems used as the sole support of ceiling-suspended fans (paddle) shall be marked by their manufacturer as suitable for this purpose and shall not support ceiling-suspended fans (paddle) that weigh more than 70 pounds (31.8 kg). For outlet boxes and outlet box systems designed to support ceiling-suspended fans (paddle) that weigh more than 35 pounds (15.9 kg), the required marking shall include the maximum weight to be supported.
06/19/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Passed