Permit Number: T17CM04315
Parcel: 13727010A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04315
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2017 ANDREW CONNOR ZONING REVIEW Approved
06/01/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide ventilation for the MDF room. Reference: Section 403.3, IMC 2012.
06/01/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2017 LOREN MAKUS ENGINEERING REVIEW Passed
06/01/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.0.1 (Site Location Map); Sheet G0.0.2 (Site Plan): Please provide a last approved site plan with each set (only two sets required).
2. Sheet G0.0.2; Applicable Codes:The 2010 is listed for accessibility. Please revise this to the 2009 ICC/ANSI A117.1.
3. Sheet G9.1.2; GWB Head Conditions B(1): Please provide the metal stud bracing size, how it connects to the partition and structure above (including connection size and quantity).
4. Sheet A1.1.1; Keynotes: Note 05 does not indicate a wall type or give stud size and spacing. Please revise the note.
5. Sheet A4.1.0; Elevation D2: Please provide the horizon5tal grab bar location per the ICC/ANSI Figure 604.5.2.
6. General: Please provide written responses to all review comments.
2. Shee
06/01/2017 ROBERT SHERRY WATER REVIEW Completed
06/01/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/01/2017 MARTIN BROWN FIRE REVIEW Approved
06/01/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed