Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T17CM04256
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/31/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Remove references to the IRC. The applicable electrical code is 2011 NEC. #2. Provide a complete one-line diagram. Include the AIC ratings of all the service equipment, complete load calcs in amps. Also include all conduit, conductor, sizes and types, grounding detail. Please consult with TEP for their approval of the service equipment configuration. As the current design does not conform with their SR manual requirements. #3. Provide more detail for the 480/277volt panel shown on the one line. Is it a termination cabinet, or a panel (load center) ? Provide for disconnecting means for the transformer as required per NEC art. 240 and 450. #4. Show branch circuit and panel designations for all EC's, heating and cooling equipment, crane hoist. #5. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE for the exterior lighting. Can be downloaded from www.tucson az.gov/pdsd. Ref: 2012 IBC sec. 107.2.1, 2011 NEC. |
| 05/31/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The minimum font size is 3/32". 2. Provide a site plan that shows the size, material, and route of the water service to the building. 3. Provide a site plan that shows the size, material, slope, and route of the building sewer. Show the location of all required cleanouts. 4. Provide the rim elevation and inverts of the upstream and downstream manholes in the public sewer. Determine if the building requires the installation of a backwater valve. 5. Provide specifications for all of the proposed plumbing fixtures. 6. Provide tempered water for the lavatory using a mixing valve listed to ASSE 1070. 7. Provide a metering faucet for the lavatory. The faucet shall deliver no more than 0.25 gallons per cycle. 8. Show the gas load and developed pipe length for all of the unit heaters. 9. Coordinate pipe sizes shown on the plumbing plan and waste piping isometric. 10. Provide cleanouts for the waste piping. The size of the cleanouts shall equal the size of the pipe. 11. Provide calculations for the roof drainage. Show the dimensions of the scuppers and provide overflow protection. 12. Clarify the roof drainage for the covered work area. |
| 05/31/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show that the building envelope and the mechanical design comply with the 2012 International Energy Conservation Code (i.e. submit COMcheck). 2. Provide heating and cooling load calculations for the heat pump and for the unit heaters. 3. Verify the balancing information for the heat pump. 4. Show the sequence of operation for the restroom exhaust fan. |
| 05/31/2017 | KROBLES1 | WATER | REVIEW | Reqs Change | Show the location of the water meter and backflow preventer serving this property. |
| 06/06/2017 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T17CM04256 - Manufacturing Use Building Plans Review (1st Review) 1560 E 17th Street TRANSMITTAL DATE: June 6, 2017 DUE DATE: June 27, 2017 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has done a cursory review of the building plans. At this time zoning cannot verify that the proposed development or building is in compliance with an approved Development Package. Until a Development Package is submitted for review zoning cannot verify compliance with the development regulations of the proposed use which is not clear on the building plans. 2. COMMENT: Zoning will review the building plans on the next submittal and do a comparison and compliance check with the development package. 3. COMMENT: Zoning will also not approve the building plans until all PDSD Commercial Plans reviewers have approved them. 4. COMMENT: Additional zoning comments may be forthcoming on the next building plan review that could be related to the DP. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Re-submittal of the building plans for review |
| 06/09/2017 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please add note to cover sheet indicating there will be absolutely no storage higher than 12'-0" above finished floor. Storage higher than this will require fire sprinklers. |
| 06/13/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 06/13/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet C1 Code Review. Total building area shall include the covered work area. Reference IBC Chapter 2 Definitions Area, Building. 2. Sheet C1 Code Review. Total building area, once covered work area is included, exceeds the maximum allowable are per Table 503. If an area increase is used due to frontage, please include calculations. 3. Sheet C1 Applicable Codes. Please include ANSI A117.1-2009 for accessibility requirements. 4. Sheet C1 Code Review. Dead end corridor is limited to 20 ft per IBC 1018.4, Exception 2 allows 50 ft where a building is provided with an automatic sprinkler system. 5. Sheet A1 Wall Types. For wall types 3 & 4, please provide details which include the anchoring and attachment to structure above. Please include the type of bracing material to be used, size and number/spacing of fasteners. 6. Sheet A1. Please provide details for accessible restroom with measurements which correlate with ANSI A117.1-2009 figures 604.3, 604.5.1 and 604.5.2. 7. Provide Special Inspection Certificate. 8. Structural Calculations. Please provide a keyplans for lintels, beams and column foundations. 9. Sheet S1. Column footings along the north side of building reference detail 1/S3 which is 7 ft. square. These column footings are drawn at 5 ft. square. Please clarify. 10. Sheet S4 Roof and Wall Panel Attachment. ICC Report 5617 is no longer valid. Please provide a valid report. 11. Provide written responses to all comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/20/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |