Permit Number: T17CM04256
Parcel: 12418053C

Address:
1560 E 17TH ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM04256
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/31/2017 ENEWCOM1 FIRE REVIEW Needs Review
05/31/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The minimum font size is 3/32".
2. Provide a site plan that shows the size, material, and route of the water service to the building.
3. Provide a site plan that shows the size, material, slope, and route of the building sewer. Show the location of all required cleanouts.
4. Provide the rim elevation and inverts of the upstream and downstream manholes in the public sewer. Determine if the building requires the installation of a backwater valve.
5. Provide specifications for all of the proposed plumbing fixtures.
6. Provide tempered water for the lavatory using a mixing valve listed to ASSE 1070.
7. Provide a metering faucet for the lavatory. The faucet shall deliver no more than 0.25 gallons per cycle.
8. Show the gas load and developed pipe length for all of the unit heaters.
9. Coordinate pipe sizes shown on the plumbing plan and waste piping isometric.
10. Provide cleanouts for the waste piping. The size of the cleanouts shall equal the size of the pipe.
11. Provide calculations for the roof drainage. Show the dimensions of the scuppers and provide overflow protection.
12. Clarify the roof drainage for the covered work area.
05/31/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Remove references to the IRC. The applicable electrical code is 2011 NEC.
#2. Provide a complete one-line diagram. Include the AIC ratings of all the service equipment, complete load calcs in amps. Also include all conduit, conductor, sizes and types, grounding detail. Please consult with TEP for their approval of the service equipment configuration. As the current design does not conform with their SR manual requirements.
#3. Provide more detail for the 480/277volt panel shown on the one line. Is it a termination cabinet, or a panel (load center) ? Provide for disconnecting means for the transformer as required per NEC art. 240 and 450.
#4. Show branch circuit and panel designations for all EC's, heating and cooling equipment, crane hoist.
#5. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE for the exterior lighting. Can be downloaded from www.tucson az.gov/pdsd.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC.
05/31/2017 MMENDIB1 ZONING REVIEW Needs Review
05/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
05/31/2017 ROBERT SHERRY WATER REVIEW Reqs Change Show the location of the water meter and backflow preventer serving this property.
05/31/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the building envelope and the mechanical design comply with the 2012 International Energy Conservation Code (i.e. submit COMcheck).
2. Provide heating and cooling load calculations for the heat pump and for the unit heaters.
3. Verify the balancing information for the heat pump.
4. Show the sequence of operation for the restroom exhaust fan.
05/31/2017 MMENDIB1 ENGINEERING REVIEW Passed
05/31/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/31/2017 GERRY KOZIOL WWM REVIEW Completed P17WX01357

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2017 KROBLES1 OUT TO CUSTOMER Completed