Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM04152
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/25/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 05/25/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 05/26/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/26/2017 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 05/26/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/26/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/26/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/08/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/08/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/09/2017 | KROBLES1 | WWM | REVIEW | Passed |