Permit Number: T17CM04143
Parcel: 117051360

Address:
222 E 6TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM04143
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/06/2017 ACONNOR1 ENGINEERING REVIEW Passed
06/06/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Verify that the total and sensible cooling capacities are supported by the cooling load calculations.
2. Provide specifications for the chimney thimble.
06/06/2017 ANDREW CONNOR ZONING REVIEW Approved
06/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the vent for the grease interceptor is able to rise vertically to at least 6" above the flood rim of the grease interceptor (i.e. the floo level) prior to running horizontally. Reference: Section 905.4, IPC 2012.
06/07/2017 GERRY KOZIOL WWM REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
06/07/2017 MMENDIB1 OUT TO CUSTOMER Completed