Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM04143
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/06/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/06/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
06/06/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the total and sensible cooling capacities are supported by the cooling load calculations. 2. Provide specifications for the chimney thimble. |
06/06/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
06/06/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/06/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the vent for the grease interceptor is able to rise vertically to at least 6" above the flood rim of the grease interceptor (i.e. the floo level) prior to running horizontally. Reference: Section 905.4, IPC 2012. |
06/07/2017 | GERRY KOZIOL | WWM | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/07/2017 | MMENDIB1 | OUT TO CUSTOMER | Completed |