Permit Number: T17CM04116
Parcel: 132130840

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04116
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2017 ANDREW CONNOR ZONING REVIEW Approved
05/24/2017 ERIC NEWCOMB MECHANICAL-COMMERCIAL REVIEW Needs Review
05/24/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/24/2017 ACONNOR1 ENGINEERING REVIEW Passed
05/24/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A100; Floor Plan: Does the existing exit door on the west wall have panic hardware per the IBC Section 1008.1.10? Please verify.
2. Sheet A110; Fixture Plan: Please provide a calculation on the plan indicating the number of required dining surfaces and seats follows the IBC Section 1108.2.9.1.
3. General: Please provide written responses to these review comments.
05/24/2017 ENEWCOM1 WATER REVIEW Needs Review
05/24/2017 ERIC NEWCOMB PLUMBING-COMMERCIAL REVIEW Needs Review
05/24/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
05/25/2017 MARTIN BROWN FIRE REVIEW Approved
06/07/2017 GERRY KOZIOL WWM REVIEW Needs Review