Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM04115
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/26/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/30/2017 | GERRY KOZIOL | WWM | REVIEW | Completed |