Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM04064
Parcel: 134031450

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04064
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2017 ANDREW CONNOR ZONING REVIEW Approved
05/23/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide a site plan for the buildings being modified. Reference: Section 107.2.5, IBC 2012.
2. Provide a COMcheck analysis of the building modifications (i.e. alterations). Reference: Sections C101.4.3, C101.4.6, and R101.4.3, IECC 2012.
05/23/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Please provide a site plan. Show the locations of panel H1 and HP.
#2. Plan sheet E1 shows all the exhaust fans branch circuits designated to panel HP. Please clarify.
#3. Indicate conduit and conductor sizes and types for the branch circuits.
#4. Is the apartment electrical plan typical for all the apartment buildings? Please indicate on the plans.
Ref : 2012 IBC sec. 107.2.1, 2011 NEC.
05/23/2017 ACONNOR1 ENGINEERING REVIEW Passed
05/23/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide a site plan to determine building layout for review and inspections.
05/23/2017 ROBERT SHERRY WATER REVIEW Completed
05/23/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/23/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/23/2017 RSHERRY1 WWM REVIEW Passed No Plumbing
05/24/2017 MARTIN BROWN FIRE REVIEW Passed