Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM04063
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/23/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 05/23/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a site plan for the buildings being modified. Reference: Section 107.2.5, IBC 2012. 2. Provide a COMcheck analysis of the building modifications (i.e. alterations). Reference: Sections C101.4.3, C101.4.6, and R101.4.3, IECC 2012. |
| 05/23/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Please provide a site plan. Show the locations of panel H1 and HP. #2. Plan sheet E1 shows all the exhaust fans branch circuits designated to panel HP. Please clarify. #3. Indicate conduit and conductor sizes and types for the branch circuits. #4. Is the apartment electrical plan typical for all the apartment buildings? Please indicate on the plans. Ref : 2012 IBC sec. 107.2.1, 2011 NEC. |
| 05/23/2017 | ACONNOR1 | ENGINEERING | REVIEW | Approved | |
| 05/23/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please provide a site plan to determine building layout for review and inspections. |
| 05/23/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/23/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/23/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/23/2017 | RSHERRY1 | WWM | REVIEW | Passed | No Plumbing |
| 05/24/2017 | MARTIN BROWN | FIRE | REVIEW | Passed |