Permit Number: T17CM04028
Parcel: 10818716A

Address:
1765 E RIVER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM04028
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2017 MMENDIB1 BUILDING-COMMERCIAL REVIEW Needs Review
05/26/2017 MMENDIB1 WATER REVIEW Needs Review
05/26/2017 MMENDIB1 WWM REVIEW Needs Review
05/31/2017 MMENDIB1 PLUMBING-COMMERCIAL REVIEW Needs Review
05/31/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response. As per the last plan review comment #2 referenced the lighting plan. The lighting plan still does not show designated symbols for the luminaires or accurate branch circuit and panel designations. Provide a complete luminaire schedule.
Ref:2012 IBC 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal requirements.
05/31/2017 MMENDIB1 MECHANICAL-COMMERCIAL REVIEW Needs Review